| Current input: |
|
0..20mA, 100Ohm |
| Voltage input: |
|
0..10V, 1MOhm |
| Network: |
|
10/100BaseT autosensing |
| Supply voltage: |
|
12-24V AC / DC using screw terminal |
| |
|
|
| Measuring unit |
|
|
| |
|
|
| Model 57641 (0..20mA, 0..10V) |
|
|
| Resolution: |
|
Current input: 2.5µA, voltage input: 1.25mV |
| Measuring error: |
|
max. 0.5% FSR (Full Scale Range 0..20mA, 0..10V) T A = 0-60°C |
| |
|
|
| Model 57642 (2x 0..20mA) |
|
|
| Resolution |
|
2x current input: 2.5µA |
| Measuring error: |
|
max. 0.5% FSR (Full Scale Range 0..20mA) T A = 0-60°C |
| |
|
|
| Model 57643 (2x 0..10V) |
|
|
| Resolution |
|
2x voltage input: 1.25mV |
| Measuring error: |
|
max. 0.5% FSR (Full Scale Range 0..10V) T A = 0-60°C |
| |
|
|
| Storage frequency: |
|
1, 5, 15, 60 min |
| Memory depth (832k): |
|
min. 79 days, max. 17 years |
| Deviation of the internal clock: |
|
max. 4.32 min. / month |
Measurement value acquisition (can be polled over the network and an alarm generated if desired): |
|
2/second |
Saving in the internal data logger |
|
1/Minute |
| |
|
|
| Other data |
|
|
| Galvanic isolation: |
|
Measuring inputs-Network: min. 500 V |
| E-mail function: |
|
Mail for sending alarms or as reporting function |
| Supply voltage: |
|
DC 12V (-5%) - 34V (+5%) AC 9Veff (-5%) - 24Veff (+5%) DC 48V (+10%) on request |
| Current consumption: |
|
AVG: 185mA @12VDC, 90mA @24VDC |
| Power supply: |
|
supplied power adapter or 12..24 V DC/AC
|
| Housing: |
|
Plastic compact housing, 105x75x22mm |
| Weight: |
|
approx. 200g |
| Ambient storage temperature: |
|
-40..+70°C |
| Ambient operating temperature: |
|
0 .. +60°C |
| Included: |
|
1x Web-IO Analog-In for top-hat rail mount 1x product CD with Management-Tool WuTility, OPC-Server, Programming examples for VB/Delphi, SNMP-MIB Reference manual in German/English Accessories: Please order #11020 Switching power supply, 100-240V/50-60Hz - 24V/0.22A DC seperately. |