Current input:
|
|
0..20mA, 100Ohm |
|
Voltage input:
|
|
0..10V, 1MOhm |
|
Network:
|
|
10/100BaseT autosensing |
|
Supply voltage:
|
|
12-24V AC / DC using screw terminal |
|
|
|
|
Measuring unit
|
|
|
|
|
|
|
Model 57641 (0..20mA, 0..10V)
|
|
|
|
Resolution:
|
|
Current input: 2.5µA, voltage input: 1.25mV |
|
Measuring error:
|
|
max. 0.5% FSR (Full Scale Range 0..20mA, 0..10V) T A = 0-60°C |
|
|
|
|
Model 57642 (2x 0..20mA)
|
|
|
|
Resolution
|
|
2x current input: 2.5µA |
|
Measuring error:
|
|
max. 0.5% FSR (Full Scale Range 0..20mA) T A = 0-60°C |
|
|
|
|
Model 57643 (2x 0..10V)
|
|
|
|
Resolution
|
|
2x voltage input: 1.25mV |
|
Measuring error:
|
|
max. 0.5% FSR (Full Scale Range 0..10V) T A = 0-60°C |
|
|
|
|
Storage frequency:
|
|
1, 5, 15, 60 min |
|
Memory depth (832k):
|
|
min. 79 days, max. 17 years |
|
Deviation of the internal clock:
|
|
max. 4.32 min. / month |
|
Measurement value acquisition (can be polled over the network and an alarm generated if desired):
|
|
2/second |
|
Saving in the internal data logger
|
|
1/Minute |
|
|
|
|
Other data
|
|
|
|
Galvanic isolation:
|
|
Measuring inputs-Network: min. 500 V |
|
E-mail function:
|
|
Mail for sending alarms or as reporting function |
|
Supply voltage:
|
|
DC 12V (-5%) - 34V (+5%) AC 9Veff (-5%) - 24Veff (+5%) DC 48V (+10%) on request |
|
Current consumption:
|
|
AVG: 185mA @12VDC, 90mA @24VDC |
|
Power supply:
|
|
supplied power adapter or 12..24 V DC/AC
|
|
Housing:
|
|
Plastic compact housing, 105x75x22mm |
|
Weight:
|
|
approx. 200g |
|
Ambient storage temperature:
|
|
-40..+70°C |
|
Ambient operating temperature:
|
|
0 .. +60°C |
|
Included:
|
|
1x Web-IO Analog-In for top-hat rail mount 1x product CD with Management-Tool WuTility, OPC-Server, Programming examples for VB/Delphi, SNMP-MIB Reference manual in German/English |
|
|
Please order power supplies separately as accessories |