0..20mA current input, 0..10V voltage input (57641)
2x 0..20mA current input (57642)
2x 0..10V voltage input (57643)
Easy Start:
Connect measurement lines and network cable
Connect supply voltage
Assign IP number
That's it!
Current input:
0..20mA, 100Ohm
Voltage input:
0..10V, 1MOhm
Network:
10/100BaseT autosensing
Supply voltage:
12-24V AC / DC using screw terminal
Measuring unit
Model 57641 (0..20mA, 0..10V)
Resolution:
Current input: 2.5µA, voltage input: 1.25mV
Measuring error:
max. 0.5% FSR (Full Scale Range 0..20mA, 0..10V) T A = 0-60°C
Model 57642 (2x 0..20mA)
Resolution
2x current input: 2.5µA
Measuring error:
max. 0.5% FSR (Full Scale Range 0..20mA) T A = 0-60°C
Model 57643 (2x 0..10V)
Resolution
2x voltage input: 1.25mV
Measuring error:
max. 0.5% FSR (Full Scale Range 0..10V) T A = 0-60°C
Storage frequency:
1, 5, 15, 60 min
Memory depth (832k):
min. 79 days, max. 17 years
Deviation of the internal clock:
max. 4.32 min. / month
Measurement value acquisition (can be polled over the network and an alarm generated if desired):
2/second
Saving in the internal data logger
1/Minute
Other data
Galvanic isolation:
Measuring inputs-Network: min. 500 V
E-mail function:
Mail for sending alarms or as reporting function
Supply voltage:
DC 12V (-5%) - 34V (+5%) AC 9Veff (-5%) - 24Veff (+5%) DC 48V (+10%) on request
Current consumption:
AVG: 185mA @12VDC, 90mA @24VDC
Power supply:
supplied power adapter or 12..24 V DC/AC
Housing:
Plastic compact housing, 105x75x22mm
Weight:
approx. 200g
Ambient storage temperature:
-40..+70°C
Ambient operating temperature:
0 .. +60°C
Included:
1x Web-IO Analog-In for top-hat rail mount 1x AC adapter 1x product CD with Management-Tool WuTility, OPC-Server, Programming examples for VB/Delphi, SNMP-MIB Reference manual in German/English
test
You may also be interested in this/these product(s)
Switching Power Supply, 100-240V/50-60Hz - 24V/1A DC
292,50 DKK