57616 Web-Thermograph Relay
Price per Unit (piece):
2.610,00 DKK
Temperature measurement using Pt100 or Pt1000 sensor
- Digital relay output
- Power provided using Power over Ethernet .
Background information:
Like all models in the Web-IO Climate series, the Web-Thermograph Relay 57616 offers everything you need to connect a temperature sensor to the computer network. An alarm can be triggered when limits are violated directly from the integrated relay, so that signal lamps or acoustic warning signals can be turned on and off. In addition, the supply voltage in accordance with IEEE 802.3af (Power-over-Ethernet) can be provided over the network cable, with both phantom power over the data pairs as well as power over the unused wire pairs (for 10/100BT) is supported. Problems with receptacles, country-specific plug types, different line voltages etc. are a thing of the past.
For cases in which PoE is planned but not yet fully implemented, it is also possible to provide power using an external power supply and screw terminals.
| Temperature sensor: |
|
Pt100/Pt1000 connection on screw terminal |
| Network: |
|
10/100BaseT autosensing |
| Supply voltage: |
|
Power-over-Ethernet (PoE) or via screw terminal with DC 18V .. 48V (+/-10%) or AC 18Veff .. 30Veff (+/-10%) |
| |
| Measuring unit |
|
|
| Sensor: |
|
Pt100/Pt1000 connection, 2-, 3- or 4-wire |
| Measuring range: |
|
W&T sensor: -50°C...180°C PT100/PT1000 measuring input: -200°C...650°C |
| Resolution: |
|
1/10°C |
Measuring error: Measuring unit |
|
| |
±0.3°C, ±0.2% |
 |
|
| PT100/1000 Sensor Class A |
|
| |
±0.15°C, ±0.2% |
 |
|
| Storage frequency: |
|
15, 30 sec., 1, 5, 15, 60 min |
| Memory depth (6MB): |
|
min. 28 weeks, max. 99 years |
| Deviation of the internal clock: |
|
max. 1 min. / month |
| |
|
|
| Semiconductor relay output |
|
|
| Digital output: |
|
1 potential-free contact, semiconductor relay |
| max. switching current: |
|
AVG 300mA AC/DC (peak 500mA) |
| max. switching voltage: |
|
39V AC/DC |
| max. switching capacity: |
|
11.7W AC/DC |
| |
|
|
| Other data |
|
|
| Measuring frequency: |
|
4 seconds |
| Galvanic isolation: |
|
Measurement inputs to network: min. 500V |
| E-mail function: |
|
Mail for sending alarms or as reporting function |
| Supply voltage: |
|
Power-over-Ethernet (PoE) or via screw terminal with DC 18V .. 48V (+/-10%) or AC 18Veff .. 30Veff (+/-10%) |
| Power consumption: |
|
AVG: 80mA @24VDC, 110mA @18VAC Max: 90mA @24VDC, 50mA @48VDC PoE Class 1 (0.44 - 3.84W) |
| Housing: |
|
Plastic compact housing, 105x75x22mm |
| Weight: |
|
approx. 200g |
| Ambient storage temperature: |
|
-40..+70°C |
| Ambient operating temperature: |
|
0 .. +60°C |
| Delivery: |
|
1x Web-Thermograph relay for DIN rail mounting 1x Pt100 sensor |
Product properties:
- Pt100/Pt1000 input and digital solid-state relay output
- NEW! Shorter memory frequency: starting at 15 seconds
- NEW! Device language selectable German/English
- Supply voltage via Power-over-Ethernet (PoE)
- Phantom power using data pairs
- Power over unused wire pairs
- Alternate external supply possible
-
Internal, battery buffered clock
The time of day continues to run even when the unit is turned off and is
immediately available after power-up!
-
Self-updating characteristic curve
 |
- Display temperature curves,
alarm monitoring and output status at a glance
- Freely selectable line color
- Freely selectable display size
- Extreme value or current value display
- Automatic or manual scaling
|
- Monitor temperatures and curves with your browser
- HTML page design user-variable
- Direct access to current temperature value, e.g., for integration into other Web pages
-
SNMP temperature polling /Alarm traps for incorporating into your existing SNMP management system
- A new measurement is available every 4 seconds!